SCHNEIDER
residual current protection relay, Vigirex RH21M, 30 mA or 300 mA, 220/240 VAC 50/60 Hz, DIN rail mounting - 56163
56163
€169.36 Excl. Tax
€203.23 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
In stock more than 25 units – Dispatched within 24/48h
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | VigiPacT |
---|---|
Device short name: | RH21M |
Product or component type: | Residual current protection relay |
Relay application: | Protection relay |
Mounting support: | DIN rail |
Earth-leakage protection class: | Type A |
Type of setting: | Selector |
Residual earth-leakage sensitity adjustment type: | Adjustable 2 settings |
Earth leakage current: | 0.03 A0.3 A |
Residual earth-leakage time delay adjustment type: | Instantaneous for 0.03 AInstantaneous for 0.3 AFixed 0.06 s for 0.3 A |
Range compatibility: | TOA earth leakage current sensor A earth leakage current sensor L earth leakage current sensor |
[Ithe] conventional enclosed thermal current: | 8 A |
Minimum load: | 10 mA at 12 V |
[Us] rated supply voltage: | 220...240 V AC 50/60 Hz 55...110 % |
Power consumption in VA: | 4 VA |
Network rated voltage: | 1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum) |
Earthing system: | ITTTTN-S |
[Uimp] rated impulse withstand voltage: | 8 kV |
Reset: | Manual reset |
Test function: | LocalRemote test |
---|---|
Monitoring: | Electronics (continuous) Power supply (continuous) Relay/sensor link (continuous) |
Type of measurement: | Earth fault current internal measurement, range: 80...100 % |
Tamperproof of settings: | Protected by sealable cover |
Connections - terminals: | Auxiliary power supply: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12Auxiliary power supply: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12Auxiliary power supply: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12Fault: screw terminal cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12Fault: screw terminal cable(s) 0.2...4 mm² rigid AWG 24...AWG 12Fault: screw terminal cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12Relay test and fault reset: screw terminal cable(s) 0.14...1 mm² flexible AWG 26...AWG 16Relay test and fault reset: screw terminal cable(s) 0.14...1.5 mm² rigid AWG 26...AWG 16Relay test and fault reset: screw terminal cable(s) 0.25...0.5 mm² flexible AWG 26...AWG 16Sensor: screw terminal cable(s) 0.14...1 mm² flexible AWG 26...AWG 16Sensor: screw terminal cable(s) 0.14...1.5 mm² rigid AWG 26...AWG 16Sensor: screw terminal cable(s) 0.25...0.5 mm² flexible AWG 26...AWG 16Voltage presence: screw terminal cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12Voltage presence: screw terminal cable(s) 0.2...4 mm² rigid AWG 24...AWG 12Voltage presence: screw terminal cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 |
Wire stripping length: | Auxiliary power supply: 7 mm for top connectionFault: 8 mm for bottom connectionRelay test and fault reset: 5 mm for bottom connectionSensor: 5 mm for top connectionVoltage presence: 8 mm for bottom connection |
Tightening torque: | Auxiliary power supply: 0.6 N.m topFault: 0.6 N.m bottomRelay test and fault reset: 0.25 N.m bottomSensor: 0.25 N.m topVoltage presence: 0.6 N.m bottom |
9 mm pitches: | 6 |
Width: | 54 mm |
Height: | 81 mm |
Depth: | 74 mm |
Product weight: | 0.3 kg |
IP degree of protection: | IP40 on front face: conforming to EN/IEC 60529IP30 on side parts: conforming to EN/IEC 60529IP20 on connection terminals: conforming to EN/IEC 60529 |
IK degree of protection: | IK07 conforming to EN 50102 |
Mechanical robustness: | Fire resistance conforming to IEC 60695-2-1IK protection 2 joules: IK07 conforming to EN 50102Vibrations 13.2...100 Hz: 0.7 gVibrations 2...13.2 Hz: +/- 1 mm |
Compatibility code: | RH21M |
In short
Reference 56163
Product Name residual current protection relay, Vigirex RH21M, 30 mA or 300 mA, 220/240 VAC 50/60 Hz, DIN rail mounting - 56163
Range Vigirex
Related Categories