SCHNEIDER
soft starter-ATS22-control 220V-power 230V(15kW)/400...440V(30kW) - ATS22D62Q
ATS22D62Q
€1,049.02 Excl. Tax
€1,258.82 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
In stock – Dispatched within 24/48h
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range of product: | Altistart 22 |
---|---|
Product or component type: | Soft starter |
Product destination: | Asynchronous motors |
Product specific application: | Pumps and fans |
Component name: | ATS22 |
Network number of phases: | 3 phases |
[Us] rated supply voltage: | 230...440 V - 15...10 % |
Motor power kW: | 15 kW 230 V30 kW 400 V30 kW 440 V |
Factory setting current: | 57 A |
Power dissipation in W: | 59 W for standard applications |
Utilisation category: | AC-53A |
Type of start: | Start with torque control (current limited to 3.5 In) |
IcL starter rating: | 62 A for connection in the motor supply line for standard applications |
IP degree of protection: | IP20 |
Assembly style: | With heat sink |
---|---|
Function available: | Internal bypass |
Supply voltage limits: | 195...484 V |
Supply frequency: | 50...60 Hz - 10...10 % |
Network frequency: | 45...66 Hz |
Device connection: | To the motor delta terminalsIn the motor supply line |
[Uc] control circuit voltage: | 230 V - 15...10 % 50/60 Hz |
Control circuit consumption: | 20 W |
Discrete output number: | 2 |
Discrete output type: | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/ORelay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
Minimum switching current: | 100 mA at 12 V DC (relay outputs) |
Maximum switching current: | 5 A 250 V AC resistive 1 relay outputs5 A 30 V DC resistive 1 relay outputs2 A 250 V AC inductive 0.4 20 ms relay outputs2 A 30 V DC inductive 7 ms relay outputs |
Discrete input number: | 3 |
Discrete input type: | (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
Discrete input voltage: | 24 V |
Discrete input logic: | Positive logic LI1, LI2, LI3 at State 0: 11 V, >= 5 mA |
Output current: | 0.4...1 Icl adjustable |
PTC probe input: | 750 Ohm |
Communication port protocol: | Modbus |
Connector type: | 1 RJ45 |
Communication data link: | Serial |
Physical interface: | RS485 multidrop |
Transmission rate: | 4800, 9600 or 19200 bps |
Installed device: | 31 |
Protection type: | Phase failure: lineThermal protection: motorThermal protection: starter |
Marking: | CE |
Type of cooling: | Forced convection |
Operating position: | Vertical +/- 10 degree |
Height: | 295 mm |
Width: | 145 mm |
Depth: | 207 mm |
Product weight: | 12 kg |
Power range: | 15...25 kW at 200...240 V 3 phases30...50 kW at 380...440 V 3 phases |
Motor starter type: | Soft starter |
In short
Reference ATS22D62Q
Product Name soft starter-ATS22-control 220V-power 230V(15kW)/400...440V(30kW) - ATS22D62Q
Related Categories