SCHNEIDER
Trip unit MicroLogic 5.2AZ, ComPacT NSX100/160/250, 3 poles, electronic basic protections, special applications, 100A - C1035Z100
C1035Z100
€649.05 Excl. Tax
€778.86 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process – Average delivery time 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | ComPacT new generation |
---|---|
Range of product: | ComPacT NSX100...250 new generation |
Product or component type: | Trip unit |
Trip unit name: | Micrologic 5.2 A-Z |
Trip unit technology: | Electronic |
Range compatibility: | ComPacT new generation NSX100ComPacT new generation NSX160ComPacT new generation NSX250 |
Device application: | 16 Hz 2/3 networks |
Poles description: | 3P |
Protected poles description: | 3D |
Trip unit protection functions: | LSI |
Protection type: | L |
[In] rated current: | 100 A at 40 °C |
[Ue] rated operational voltage: | 250/500 V AC 16 Hz 2/3 |
Mounting mode: | Fixed |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
---|---|
Long time pick-up adjustment range: | 40...100 A |
Long time delay adjustment type: | Adjustable |
[tr] long-time delay adjustment range: | 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Adjustable |
[tsd] short-time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
Instantaneous pick-up adjustment type Ii: | Adjustable |
Instantaneous pick-up adjustment range: | 1.5...12 x In |
Earth-leakage protection: | Without |
Zone selective interlocking ZSI: | With |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
Display type: | LCD display |
Type of measurement: | Ammeter |
Communication of data: | Energy meteringProtection and alarm settingsTime-stamped histories and event tablesInstantaneous and demand valuesMaintenance indicatorsDemand current and powerPower qualityMaximeters/minimeters |
Electrical data recording: | Maintenance indicators |
In short
Reference C1035Z100
Product Name Trip unit MicroLogic 5.2AZ, ComPacT NSX100/160/250, 3 poles, electronic basic protections, special applications, 100A - C1035Z100
Range ComPacT nouvelle génération
Related Categories