Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, MicroLogic 2.2 trip unit 40A - C10B32D040

C10B32D040

€270.88 Excl. Tax
€325.06 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range: ComPacT new generation
Product name: ComPacT NSX new generation
Range of product: ComPacT NSX100...250 new generation
Device short name: NSX100B
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
[In] rated current: 40 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-220 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-215 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: B 25 kA 415 V AC
Trip unit name: Micrologic 2.2
Trip unit technology: Electronic
Trip unit protection functions: LSoI
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-225 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-220 kA at 440 V AC 50/60 Hz conforming to IEC 60947-27 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 50000 cycles
Electrical durability: 50000 cycles at 440 V In/230000 cycles at 440 V In20000 cycles at 690 V In/210000 cycles at 690 V In
Power dissipation per pole: 1.34 W
Mounting support: Backplate
Mounting position: Horizontal and verticalFlat on the back
Upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L
Trip unit rating: 40 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 18...40 A
Long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 400 s at 1.5 x Ir16 s at 6 x Ir11 s at 7.2 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 600 A
Earth-leakage protection: Without
Zone selective interlocking ZSI: Without
Number of slots: 5 slot(s)
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Width: 105 mm
Height: 161 mm
Depth: 86 mm
Net weight: 2.05 kg
Compatibility code: NSX100
In short
Reference C10B32D040
Product Name Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, MicroLogic 2.2 trip unit 40A - C10B32D040
Range ComPacT nouvelle génération