Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from December 30th to January 1st! Shipments will resume on January 2nd ⚠️
SCHNEIDER

Circuit breaker, ComPacT NSX100N, 50kA/415VAC, 3 poles, TMD trip unit 100A - C10N3TM100

C10N3TM100

€264.20 Excl. Tax
€317.04 Inc. Tax
available In stock more than 100 units – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range: ComPacT new generation
Product name: ComPacT NSX new generation
Range of product: ComPacT NSX100...250 new generation
Device short name: NSX100N
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
[In] rated current: 100 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit protection functions: LI
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-250 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 kA at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA at 500 V AC 50/60 Hz conforming to IEC 60947-235 kA at 525 V AC 50/60 Hz conforming to IEC 60947-210 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 50000 cycles
Electrical durability: 50000 cycles at 440 V In/230000 cycles at 440 V In20000 cycles at 690 V In/210000 cycles at 690 V In
Power dissipation per pole: 8.8 W
Mounting support: Backplate
Mounting position: Horizontal and verticalFlat on the back
Upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L
Trip unit rating: 100 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable
Long time pick-up adjustment range: 0.7...1 x In
Long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 120...400 s at 1.5 x In15 s at 6 x Ir
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 800 A
Earth-leakage protection: Without
Number of slots: 5 slot(s)
Width: 105 mm
Height: 161 mm
Depth: 86 mm
Net weight: 2.05 kg
Compatibility code: NSX100
In short
Reference C10N3TM100
Product Name Circuit breaker, ComPacT NSX100N, 50kA/415VAC, 3 poles, TMD trip unit 100A - C10N3TM100
Range ComPacT nouvelle génération
Related Categories