SCHNEIDER
circuit breaker ComPacT NSX100R, 200 kA at 415 VAC, MicroLogic 6.2 E-M trip unit 25 A, 3 poles 3d - C10R36M025
C10R36M025
€1,050.16 Excl. Tax
€1,260.19 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process – Average delivery time 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | ComPacT new generation |
---|---|
Product name: | ComPacT NSX new generation |
Range of product: | ComPacT NSX100...250 new generation |
Device short name: | NSX100R |
Product or component type: | Circuit breaker |
Device application: | Motor protection |
Poles description: | 3P |
Protected poles description: | 3D |
[In] rated current: | 25 A at 65 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-280 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-245 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | R 200 kA 415 V AC |
Trip unit name: | Micrologic 6.2 E-M |
Trip unit technology: | Electronic |
Trip unit protection functions: | LSIG |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-280 kA at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA at 525 V AC 50/60 Hz conforming to IEC 60947-245 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 20000 cycles |
Electrical durability: | 20000 cycles at 440 V In/210000 cycles at 440 V In10000 cycles at 690 V In/25000 cycles at 690 V In |
Power dissipation per pole: | 0.53 W |
Mounting support: | Backplate |
Mounting position: | Horizontal and verticalFlat on the back |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 35 mm |
Protection type: | L |
Trip unit rating: | 25 A at 65 °C |
Motor tripping class: | 5103020 |
Complementary motor protection: | Protracted starting timePhase unbalanceUnderloadStalled rotor |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
Long time pick-up adjustment range: | 12...25 A |
Long time delay adjustment type: | Adjustable |
[tr] long-time delay adjustment range: | 120 s at 1.5 x Ir for trip class 56.5 s at 6 x Ir for trip class 55 s at 7.2 x Ir for trip class 5240 s at 1.5 x Ir for trip class 1013.5 s at 6 x Ir for trip class 1010 s at 7.2 x Ir for trip class 10480 s at 1.5 x Ir for trip class 2026 s at 6 x Ir for trip class 2020 s at 7.2 x Ir for trip class 20720 s at 1.5 x Ir for trip class 3038 s at 6 x Ir for trip class 3030 s at 7.2 x Ir for trip class 30 |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable |
[Isd] short-time pick-up adjustment range: | 5...13 x Ir |
Short-time delay adjustment type: | Fixed |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 425 A |
Ground-fault pick-up adjustment type: | Adjustable 9 settings |
[Ig] ground-fault pick-up adjustment range: | 0.6...1 x InIg enable on/off |
Ground-fault time delay adjustment type -tg: | Adjustable 5 settings |
[tg] ground-fault time delay adjustment range: | 0...0.4 s |
Earth-leakage protection: | Without |
Zone selective interlocking ZSI: | With |
Number of slots: | 5 slot(s) |
Local signalling: | Flashing LED (green) for ready to operateLED 95 % Ith (red) for temperature over set point |
Display type: | LCD display |
Type of measurement: | Energy meter |
Communication of data: | Maximeters/minimetersPower qualityPhase sequenceDemand current and powerMaintenance indicatorsProtection and alarm settingsInstantaneous and demand valuesThermal image functionEnergy meteringTime-stamped histories and event tables |
Width: | 105 mm |
Height: | 161 mm |
Depth: | 86 mm |
Net weight: | 2.05 kg |
Compatibility code: | NSX100 |
In short
Reference C10R36M025
Product Name circuit breaker ComPacT NSX100R, 200 kA at 415 VAC, MicroLogic 6.2 E-M trip unit 25 A, 3 poles 3d - C10R36M025
Range ComPacT nouvelle génération
Related Categories