Technical informations
Range: ComPacT new generation
Range of product: ComPacT NSX100...250 new generation
Product or component type: Trip unit
Trip unit name: Micrologic 5.2 E
Trip unit technology: Electronic
Range compatibility: ComPacT new generation NSX160ComPacT new generation NSX250
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
Trip unit protection functions: LSI
Protection type: L
[In] rated current: 160 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Mounting mode: Fixed
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 63...160 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0...0.4 s I²t=off0.1...0.4 s I²t=on
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...15 x In
Earth-leakage protection: Without
Zone selective interlocking ZSI: With
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Display type: LCD display
Type of measurement: Energy meter
Communication of data: Energy meteringProtection and alarm settingsTime-stamped histories and event tablesInstantaneous and demand valuesMaintenance indicatorsDemand current and powerPower qualityMaximeters/minimeters
Electrical data recording: Maintenance indicators
In short