SCHNEIDER
trip unit MicroLogic 2.2 for ComPacT NSX 250 circuit breakers, electronic, rating 250A, 3 poles 3d - C2532D250
C2532D250
€332.03 Excl. Tax
€398.44 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
In stock more than 100 units – Dispatched within 24/48h
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | ComPacT new generation |
---|---|
Range of product: | ComPacT NSX100...250 new generation |
Product or component type: | Trip unit |
Trip unit name: | Micrologic 2.2 |
Trip unit technology: | Electronic |
Range compatibility: | ComPacT new generation NSX250 |
Device application: | Distribution |
Poles description: | 3P |
Protected poles description: | 3D |
Trip unit protection functions: | LSoI |
Protection type: | L |
[In] rated current: | 250 A at 40 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Mounting mode: | Fixed |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
---|---|
Long time pick-up adjustment range: | 100...250 A |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 11 s at 7.2 x Ir16 s at 6 x Ir400 s at 1.5 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Fixed |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 3000 A |
Earth-leakage protection: | Without |
Zone selective interlocking ZSI: | Without |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
In short
Reference C2532D250
Product Name trip unit MicroLogic 2.2 for ComPacT NSX 250 circuit breakers, electronic, rating 250A, 3 poles 3d - C2532D250
Range ComPacT nouvelle génération
Related Categories