SCHNEIDER
Circuit breaker ComPacT NSX400K, 36kA at 800VAC, 10kA at 1000VAC, MicroLogic 2.3 trip unit, 250A, 4 poles 4d - C40K42D250
C40K42D250
€2,126.95 Excl. Tax
€2,552.34 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process – Average delivery time 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | ComPacT |
---|---|
Range of product: | ComPact NSX400...630 |
Device short name: | ComPacT NSX400K |
Product or component type: | Circuit breaker |
Device application: | Special application |
Poles description: | 4P |
Protected poles description: | 3t3t + N/24t |
Neutral position: | Left |
[In] rated current: | 250 A at 40 °C |
[Ue] rated operational voltage: | 800...1000 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 36 kA Icu at 800 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | K 10 kA 1000 V AC |
Trip unit name: | Micrologic 2.3 |
Trip unit technology: | Electronic |
Trip unit protection functions: | LSoI |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 1000 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 10 kA at 800 V AC 50/60 Hz conforming to IEC 60947-210 kA at 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 15000 cycles |
Electrical durability: | 1000 cycles at 1000 V In |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 45 mm |
Protection type: | L |
Trip unit rating: | 250 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
Long time pick-up adjustment range: | 70...250 A |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 11 s at 7.2 x Ir16 s at 6 x Ir400 s at 1.5 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Fixed |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 3000 A |
Earth-leakage protection: | Without |
Neutral protection setting: | 0.5 x Ir (3t + N/2)1 x Ir (4t)No protection (3t) |
Zone selective interlocking ZSI: | Without |
Number of slots: | 6 slot(s) |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
Width: | 185 mm |
Height: | 255 mm |
Depth: | 110 mm |
Net weight: | 7.9 kg |
In short
Reference C40K42D250
Product Name Circuit breaker ComPacT NSX400K, 36kA at 800VAC, 10kA at 1000VAC, MicroLogic 2.3 trip unit, 250A, 4 poles 4d - C40K42D250
Range
Related Categories