Technical informations
Range: ComPacT new generation
Range of product: ComPacT NSX400...630 new generation
Product or component type: Trip unit
Trip unit name: Micrologic 7.3 E
Trip unit technology: Electronic
Range compatibility: ComPacT new generation NSX630
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
Trip unit protection functions: LSIR
Protection type: L
[In] rated current: 570 A at 40 °C
[Ue] rated operational voltage: 440 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Mounting mode: Fixed
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 250...570 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0...0.4 s
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...11 x In
Earth-leakage protection: Integrated
Earth-leakage protection class: Class A
Residual earth-leakage sensitity adjustment type: Adjustable
[I?n] residual earth-leakage sensitive adjustment: 0.3 A0.5 A1 A3 A5 A10 A
Operating mode: OFF using the I?n rotary switch
Residual earth-leakage time delay adjustment type: Adjustable
[?t] residual earth-leakage time delay adjustment: 0 ms60 ms150 ms500 ms1 s
Zone selective interlocking ZSI: Without
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Display type: LCD display
Type of measurement: Energy meter
Communication of data: Power qualityEarth leakage currentProtection and alarm settingsMaintenance indicatorsMaximeters/minimetersEnergy meteringDemand current and powerInstantaneous and demand valuesTest reportsTime-stamped histories and event tables