Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

Thermal magnetic circuit breaker, TeSys GB2, 1P, 8 A, Icu 1.5 kA@240 V - GB2CB14

GB2CB14

€12.55 Excl. Tax
€15.06 Inc. Tax
available In stock – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range: TeSys
Product name: TeSys GB2
Device short name: GB2
Product or component type: Circuit breaker
Device application: Control
Poles description: 1P
Network type: AC/DC
Utilisation category: Category A conforming to IEC 60947-2DC-12 conforming to IEC 60947-5-1DC-13 conforming to IEC 60947-5-1
Network frequency: 50/60 Hz conforming to IEC 60947-2
Breaking capacity: 3 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-21.5 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-21.5 kA Icu at 24 V DC conforming to IEC 60947-21 kA Icu at 48 V DC conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity: 75 % at 110 V AC 50/60 Hz conforming to IEC 60947-275 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technology: Thermal-magnetic
Magnetic tripping current: 108 A
Mounting mode: By clips
Mounting support: PlateRail
Mounting position: VerticalHorizontal
Control type: Toggle
[In] rated current: 8 A
[Ue] rated operational voltage: 250 V AC 50/60 Hz conforming to IEC 60947-2277 V AC 60 Hz conforming to CSA C22.2 No 235277 V AC 60 Hz conforming to UL 107748 V DC
[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 60947-2
Power dissipation per pole: 2 W
Mechanical durability: 8000 cycles
Electrical durability: 8000 cycles
Connections - terminals: Connector 1 cable(s) 0.75...6 mm²solid without cable endConnector 2 cable(s) 0.75...4 mm²solid without cable endConnector 1 cable(s) 0.75...4 mm²flexible with cable endConnector 2 cable(s) 0.75...2.5 mm²flexible with cable end
Tightening torque: 1.2 N.m on connector
Mechanical robustness: Shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27Vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6
Quantity per set: Set of 6
9 mm pitches: 2
Height: 74 mm
Width: 15 mm
Depth: 67 mm
Compatibility code: GB2
In short
Reference GB2CB14
Product Name Thermal magnetic circuit breaker, TeSys GB2, 1P, 8 A, Icu 1.5 kA@240 V - GB2CB14
Range TeSys
Device function Contrôle
Related Categories