Technical informations
Range: | TeSys |
---|---|
Product name: | TeSys GB2 |
Device short name: | GB2 |
Product or component type: | Circuit breaker |
Device application: | Control |
Poles description: | 2P |
Network type: | AC/DC |
Utilisation category: | Category A conforming to IEC 60947-2DC-12 conforming to IEC 60947-5-1DC-13 conforming to IEC 60947-5-1 |
Network frequency: | 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity: | 50 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-21.5 kA Icu at 24 V DC conforming to IEC 60947-21 kA Icu at 48 V DC conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity: | 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-250 % at 110 V AC 50/60 Hz conforming to IEC 60947-225 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Trip unit technology: | Thermal-magnetic |
Magnetic tripping current: | 14 A |
Mounting mode: | By clips |
---|---|
Mounting support: | PlateRail |
Mounting position: | VerticalHorizontal |
Control type: | Toggle |
[In] rated current: | 1 A |
[Ue] rated operational voltage: | 415 V AC 50/60 Hz conforming to IEC 60947-248 V DC |
[Uimp] rated impulse withstand voltage: | 4 kV conforming to IEC 60947-2 |
Power dissipation per pole: | 2 W |
Mechanical durability: | 8000 cycles |
Electrical durability: | 8000 cycles |
Connections - terminals: | Connector 1 cable(s) 0.75...6 mm²solid without cable endConnector 2 cable(s) 0.75...4 mm²solid without cable endConnector 1 cable(s) 0.75...4 mm²flexible with cable endConnector 2 cable(s) 0.75...2.5 mm²flexible with cable end |
Tightening torque: | 1.2 N.m on connector |
Mechanical robustness: | Shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27Vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6 |
Quantity per set: | Set of 3 |
9 mm pitches: | 4 |
Height: | 74 mm |
Width: | 30 mm |
Depth: | 70 mm |
Product weight: | 0.115 kg |
Compatibility code: | GB2 |