Technical informations
Range of product: | TeSys D |
---|---|
Range: | TeSys |
Product name: | TeSys D |
Product or component type: | Contactor |
Device short name: | LC1D |
Contactor application: | Resistive load |
Utilisation category: | AC-1 |
Poles description: | 4P |
Pole contact composition: | 4 NO |
[Ue] rated operational voltage: | Power circuit: Power circuit: |
[Ie] rated operational current: | 200 A (at |
Control circuit type: | AC at 50/60 Hz |
[Uc] control circuit voltage: | 230 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947 |
Overvoltage category: | III |
[Ith] conventional free air thermal current: | 200 A (at 60 °C) for power circuit |
Irms rated making capacity: | 1260 A at 440 V for power circuit conforming to IEC 60947 |
Rated breaking capacity: | 1100 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current: | 250 A 40 °C - 10 min for power circuit550 A 40 °C - 1 min for power circuit950 A 40 °C - 10 s for power circuit1100 A 40 °C - 1 s for power circuit |
Associated fuse rating: | 250 A gG at 200 A gG at |
Average impedance: | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
[Ui] rated insulation voltage: | Power circuit: 600 V CSA certifiedPower circuit: 600 V UL certifiedPower circuit: 1000 V conforming to IEC 60947-4-1 |
Electrical durability: | 0.8 Mcycles 200 A AC-1 at Ue |
Power dissipation per pole: | 24 W AC-1 |
Protective cover: | With |
Mounting support: | RailPlate |
Standards: | CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508 |
Product certifications: | ULGOSTRINADNVCSABVLROS (Lloyds register of shipping)GLCCCUKCA |
Connections - terminals: | Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...2.5 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1...2.5 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²solid without cable endPower circuit: connector 1 cable(s) 10...120 mm²flexible without cable endPower circuit: connector 2 cable(s) 10...50 mm²flexible without cable endPower circuit: connector 1 cable(s) 10...120 mm²flexible with cable endPower circuit: connector 2 cable(s) 10...50 mm²flexible with cable endPower circuit: connector 1 cable(s) 10...120 mm²solid without cable endPower circuit: connector 2 cable(s) 10...50 mm²solid without cable end |
Tightening torque: | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmControl circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2Power circuit: 12 N.m - on connector hexagonal screw head 4 mm |
Operating time: | 6...20 ms opening20...50 ms closing |
Safety reliability level: | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Mechanical durability: | 8 Mcycles |
Maximum operating rate: | 2400 cyc/h 60 °C |
Coil technology: | Built-in bidirectional peak limiting diode suppressor |
---|---|
Control circuit voltage limits: | 0.3...0.5 Uc (-40...70 °C):drop-out AC 50/60 Hz0.8...1.15 Uc (-40...55 °C):operational AC 50/60 Hz1...1.15 Uc (55...70 °C):operational AC 50/60 Hz |
Inrush power in VA: | 280...350 VA 60 Hz cos phi 0.8 (at 20 °C)280...350 VA 50 Hz cos phi 0.8 (at 20 °C) |
Hold-in power consumption in VA: | 2...18 VA 60 Hz cos phi 0.3 (at 20 °C)2...18 VA 50 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation: | 3...8 W at 50/60 Hz |
Contact compatibility: | M14 |
Compatibility code: | LC1D |