Technical informations
Range of product: TeSys D
Range: TeSys
Product name: TeSys D
Product or component type: Contactor
Device short name: LC1D
Contactor application: Resistive load
Utilisation category: AC-1
Poles description: 4P
Pole contact composition: 2 NO + 2 NC
[Ue] rated operational voltage: Power circuit: Power circuit:
[Ie] rated operational current: 60 A (at
Control circuit type: AC at 50 Hz
[Uc] control circuit voltage: 48 V AC 50 Hz
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Overvoltage category: III
[Ith] conventional free air thermal current: 60 A (at 60 °C) for power circuit
Irms rated making capacity: 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 320 A 40 °C - 10 s for power circuit720 A 40 °C - 1 s for power circuit72 A 40 °C - 10 min for power circuit165 A 40 °C - 1 min for power circuit
Associated fuse rating: 80 A gG at 80 A gG at
Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V CSA certifiedPower circuit: 600 V UL certifiedPower circuit: 690 V conforming to IEC 60947-4-1
Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue
Power dissipation per pole: 5.4 W AC-1
Protective cover: Without
Mounting support: RailPlate
Standards: CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications: GOSTBVCSAULCCCDNVLROS (Lloyds register of shipping)RINAGLUKCA
Connections - terminals: Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable endPower circuit: screw clamp terminals 1 cable(s) 1...35 mm²flexible without cable endPower circuit: screw clamp terminals 2 cable(s) 1...25 mm²flexible without cable endPower circuit: screw clamp terminals 1 cable(s) 1...35 mm²flexible with cable endPower circuit: screw clamp terminals 2 cable(s) 1...25 mm²flexible with cable endPower circuit: screw clamp terminals 1 cable(s) 1...35 mm²solid without cable endPower circuit: screw clamp terminals 2 cable(s) 1...25 mm²solid without cable end
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2Power circuit: 8 N.m - on screw clamp terminals - cable 25...35 mm² hexagonal screw head 4 mmPower circuit: 5 N.m - on screw clamp terminals - cable 1...25 mm² hexagonal screw head 4 mm
Operating time: 4...19 ms opening12...26 ms closing
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6 Mcycles
Maximum operating rate: 3600 cyc/h 60 °C
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.8...1.1 Uc (-40...60 °C):operational AC 50 Hz0.3...0.6 Uc (-40...70 °C):drop-out AC 50 Hz1...1.1 Uc (60...70 °C):operational AC 50 Hz
Inrush power in VA: 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation: 4...5 W at 50 Hz
Contact compatibility: M1