SCHNEIDER

TeSys LC1D - contacteur - 4P - AC-1 440V - 60A - bobine 48Vca  - LC1DT60AE7

LC1DT60AE7

€132.58 Excl. Tax
€159.10 Inc. Tax
available In stock – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range of product: TeSys D
Range: TeSys
Product name: TeSys D
Product or component type: Contactor
Device short name: LC1D
Contactor application: Resistive load
Utilisation category: AC-1
Poles description: 4P
Pole contact composition: 4 NO
[Ue] rated operational voltage:
[Ie] rated operational current: 60 A (
Control circuit type: AC 50/60 Hz
[Uc] control circuit voltage: 48 V AC 50/60 Hz
Auxiliary contact composition: 1 NO + 1 NC
[Uimp] rated impulse withstand voltage: Conforming to IEC 60947
Overvoltage category: III
[Ith] conventional free air thermal current: 60 A at 10 A at
Irms rated making capacity: 800 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 100 A 1 s signalling circuit120 A 500 ms signalling circuit140 A 100 ms signalling circuit320 A 720 A 72 A 165 A
Associated fuse rating: 80 A gG at 80 A gG at 10 A gG for signalling circuit conforming to IEC 60947-5-1
Average impedance: 1.6 mOhm at 50 Hz - Ith 60 A for power circuit
[Ui] rated insulation voltage: 600 V for power circuit certifications CSA600 V for power circuit certifications UL690 V for power circuit conforming to IEC 60947-4-1690 V for signalling circuit conforming to IEC 60947-1600 V for signalling circuit certifications CSA600 V for signalling circuit certifications UL
Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue
Power dissipation per pole: 5.8 W AC-1
Protective cover: With
Mounting support: RailPlate
Standards: CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications: DNVBVLROSULGLGOSTCCCRINACSA
Connections - terminals: Control circuit
Tightening torque: Control circuit
Operating time: 12...26 ms closing4...19 ms opening
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6 Mcycles
Operating rate: 3600 cyc/h at
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz0.8...1.1 Uc operational at 60 °C, AC 50 Hz0.85...1.1 Uc operational at 60 °C, AC 60 Hz
Inrush power in VA: 140 VA at 20 °C (cos ? 0.75) 60 Hz160 VA at 20 °C (cos ? 0.75) 50 Hz
Hold-in power consumption in VA: 13 VA at 20 °C (cos ? 0.3) 60 Hz15 VA at 20 °C (cos ? 0.3) 50 Hz
Heat dissipation: 4...5 W at 50/60 Hz
Auxiliary contacts type: Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching current: 5 mA for signalling circuit
Minimum switching voltage: 17 V for signalling circuit
Non-overlap time: 1.5 ms on de-energisation (between NC and NO contact)1.5 ms on energisation (between NC and NO contact)
Insulation resistance: > 10 MOhm for signalling circuit
In short
Reference LC1DT60AE7
Product Name TeSys LC1D - contacteur - 4P - AC-1 440V - 60A - bobine 48Vca  - LC1DT60AE7
Range TeSys
Related Categories