Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 630 A - coil 400 V AC - LC1F630V7

LC1F630V7

Obsolete product, here is the proposed substitution for the reference LC1F630V7 : LC1G630LSEA
Technical informations
Range of product: TeSys F
Range: TeSys
Product name: TeSys F
Product or component type: Contactor
Device short name: LC1F
Contactor application: Motor controlResistive load
Utilisation category: AC-3AC-1AC-4
Poles description: 3P
Pole contact composition: 3 NO
[Ue] rated operational voltage:
[Ie] rated operational current: 1000 A (at 630 A (at
Motor power kW: 335 kW at 380...400 V AC 50/60 Hz (AC-3)375 kW at 415 V AC 50/60 Hz (AC-3)400 kW at 440 V AC 50/60 Hz (AC-3)400 kW at 500 V AC 50/60 Hz (AC-3)450 kW at 660...690 V AC 50/60 Hz (AC-3)450 kW at 1000 V AC 50/60 Hz (AC-3)200 kW at 220...230 V AC 50/60 Hz (AC-3)100 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit type: AC at 40...400 Hz
[Uc] control circuit voltage: 400 V AC 40...400 Hz
[Uimp] rated impulse withstand voltage: 8 kV
Overvoltage category: III
[Ith] conventional free air thermal current: 1000 A (at 40 °C)1250 A
Rated breaking capacity: 5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 5050 A 40 °C - 10 s4400 A 40 °C - 30 s3400 A 40 °C - 1 min2200 A 40 °C - 3 min1600 A 40 °C - 10 min
Associated fuse rating: 1000 A gG at 630 A aM at
Average impedance: 0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-11500 V conforming to VDE 0110 group C
Power dissipation per pole: 120 W AC-148 W AC-3
Mounting support: Plate
Standards: EN 60947-1EN 60947-4-1JIS C8201-4-1IEC 60947-4-1IEC 60947-1
Product certifications: DNVBVRINALROS (Lloyds register of shipping)CSAABSULRMRoSCBUKCA
Connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable endPower circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mmPower circuit: bolted connection
Tightening torque: Control circuit: 1.2 N.mPower circuit: 58 N.m
Control circuit voltage limits: Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)Drop-out: 0.25...0.5 Uc 40...400 Hz (at 55 °C)
Inrush power in VA: 1650 VA 40...400 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA: 22 VA 40...400 Hz cos phi 0.9 (at 20 °C)
Heat dissipation: 20 W
Operating time: 40...80 ms closing100...200 ms opening
Mechanical durability: 5 Mcycles
Maximum operating rate: 1200 cyc/h 55 °C
Compatibility code: LC1F
Power range: 250...500 kW at 380...440 V 3 phases110...220 kW at 200...240 V 3 phases250...500 kW at 480...500 V 3 phases
Motor starter type: Direct on-line contactor
Contactor coil voltage: 400 V AC standard
In short
Reference LC1F630V7
Product Name TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 630 A - coil 400 V AC - LC1F630V7
Range TeSys
Related Categories