SCHNEIDER
Contacteur TeSys LC1F 3P AC3 440V 800 A bobine 220 à 230 V CC - LC1F800MW
LC1F800MW
Obsolete product, here is the proposed substitution for the reference LC1F800MW : LC1G800KUEN
Technical informations
Range of product: | TeSys F |
---|---|
Range: | TeSys |
Product name: | TeSys F |
Product or component type: | Contactor |
Device short name: | LC1F |
Contactor application: | Motor controlResistive load |
Motor power kW: | 450 kW at 440 V AC 50/60 Hz AC-3450 kW at 1000 V AC 50/60 Hz AC-3450 kW at 500 V AC 50/60 Hz AC-3475 kW at 660?690 V AC 50/60 Hz AC-3110 kW at 400 V AC 50/60 Hz AC-4450 kW at 380...400 V AC 50/60 Hz AC-3450 kW at 415 V AC 50/60 Hz AC-3250 kW at 220...230 V AC 50/60 Hz AC-3 |
Control circuit type: | AC 40...400 HzDC standard |
[Uc] control circuit voltage: | 220...230 V DC220...240 V AC 40...400 Hz |
[Uimp] rated impulse withstand voltage: | 8 kV |
Overvoltage category: | III |
[Ith] conventional free air thermal current: | 1000 A at |
Rated breaking capacity: | 6400 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current: | 5500 A 4600 A 3600 A 2600 A 1700 A |
Associated fuse rating: | 1000 A gG at 800 A aM at |
Average impedance: | 0.12 mOhm at 50 Hz - Ith 1000 A |
[Ui] rated insulation voltage: | 1000 V conforming to IEC 60947-4-11500 V conforming to VDE 0110 group C |
Power dissipation per pole: | 77 W AC-3120 W AC-1 |
Mounting support: | Plate |
Standards: | EN 60947-1EN 60947-4-1IEC 60947-1IEC 60947-4-1JEM 1038 |
Product certifications: | CSAGLULLROS |
Connections - terminals: | Control circuit |
Tightening torque: | Control circuit |
Operating time: | 40...50 ms opening60...80 ms closing |
Mechanical durability: | 5 Mcycles |
Operating rate: | 600 cyc/h at |
Utilisation category: | AC-1AC-3AC-4 |
---|---|
Poles description: | 3P |
Pole contact composition: | 3 NO |
[Ue] rated operational voltage: | |
[Ie] rated operational current: | 1000 A (800 A ( |
Control circuit voltage limits: | 0.3...0.5 Uc at 55 °C drop-out0.85...1.1 Uc at 55 °C operational |
Inrush power in W: | 1900 W at 20 °C |
Hold-in power consumption in W: | 12 W at 20 °C |
Heat dissipation: | 12 W |
Motor power range AC-3: | 250...500 kW 380...440 V 3 phases110...220 kW 200...240 V 3 phases250...500 kW 480...500 V 3 phases250...500 kW 200...240 V 3 phases |
Motor starter type: | Direct on-line contactor |
Contactor coil voltage: | 230 V AC240 V AC220 V DC standard230 V DC standard220 V AC standard |
In short
Reference LC1F800MW
Product Name Contacteur TeSys LC1F 3P AC3 440V 800 A bobine 220 à 230 V CC - LC1F800MW
Range TeSys
Related Categories