Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

Multifunction control unit, TeSys U, 3-12A, 1P/3P motors, protection & diagnostic, class 5-30, coil 24V DC - LUCM12BL

LUCM12BL

€200.74 Excl. Tax
€240.89 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range: TeSys
Range of product: TeSys Ultra
Product name: TeSys Ultra
Device short name: LUCM
Product or component type: Multifunction control unit
Device application: Motor controlMotor protection
Product specific application: Most sophisticated control and protection requirements, with display
Function available: Protection against overload and short-circuitManual or automatic resetProtection function alarmProtection against phase failure and phase imbalanceLog functionMonitoring function, indication of main motor parametersOverload, no-load runningEarth fault protectionDifferentiation of thermal overload and magnetic fault
Product compatibility: Power base LUB12Power base LUB32Power base LUB38Power base LUB120Power base LUB320Power base LUB380Reversing contactor breaker LU2B12BLReversing contactor breaker LU2B32BLReversing contactor breaker LU2B38BL
[Ue] rated operational voltage: 690 V AC
Network frequency: 40...60 Hz
Load type: 3-phase motor - cooling: self-cooled - setting factory setting3-phase motor - cooling: self-cooled, force cooled - setting settableSingle-phase motor - cooling: self-cooled, force cooled - setting settable
Utilisation category: AC-41AC-43AC-44
Motor power kW: 5.5 kW at 400...440 V AC 50/60 Hz for 3 phases motors5.5 kW at 500 V AC 50/60 Hz for 3 phases motors9 kW at 690 V AC 50/60 Hz for 3 phases motors2.2 kW at 400...440 V AC 50/60 Hz for 1 phase motors
Thermal protection adjustment range: 3...12 A
Thermal overload class: Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to IEC 60947-6-2Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to UL 508
Tripping threshold: 14.2 x Ir +/- 20 %
[Uc] control circuit voltage: 24 V DC
Control circuit voltage limits: 20...28 V for DC circuit 24 V in operation14.5 V for DC circuit 24 V drop-out
Typical current consumption: 150 mA at 24 V DC I maximum while closing with LUB12200 mA at 24 V DC I maximum while closing with LUB32200 mA at 24 V DC I maximum while closing with LUB3870 mA at 24 V DC I rms sealed with LUB1275 mA at 24 V DC I rms sealed with LUB3275 mA at 24 V DC I rms sealed with LUB38
Heat dissipation: 1.7 W for control circuit with LUB121.8 W for control circuit with LUB321.8 W for control circuit with LUB380.8 W for external auxiliary circuit
Operating time: 35 ms opening with LUB12 for control circuit35 ms opening with LUB32 for control circuit35 ms opening with LUB38 for control circuit75 ms closing with LUB12 for control circuit65 ms closing with LUB32 for control circuit65 ms closing with LUB38 for control circuit
Physical interface: RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s
Return time:
Messages display capacity: 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir
Reset: Automatic reset - setting: setting rangeManual - setting: factory settingManual - setting: setting rangeRemote reset - setting: setting range
Time before reset: 1...1000 s - reset manual or automatic reset - setting settable120 s - reset manual - setting factory setting
User language: English - setting factory settingEnglish, French, German, Italian, Spanish - setting settable
Information displayed: Average current (factory setting)Average current (settable)Cause of last 5 faults (settable)Current in phase (settable)Earth leakage current (settable)Phase imbalance (settable)Thermal state of motor (settable)
Standards: EN 60947-6-2IEC 60947-6-2UL 60947-4-1, with phase barrierCSA C22.2 No 60947-4-1, with phase barrier
Product certifications: CEULCSACCCEACASEFAATEXMarine
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-6-2600 V conforming to UL 60947-4-1600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-6-2
Safe separation of circuit: 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing mode: Plug-in (front face)
Width: 45 mm
Height: 66 mm
Depth: 60 mm
Net weight: 0.175 kg