SCHNEIDER
Multifunction control unit, TeSys U, 3-12A, 1P/3P motors, protection & diagnostic, class 5-30, coil 24V DC - LUCM12BL
LUCM12BL
€200.74 Excl. Tax
€240.89 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process – Average delivery time 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
Range: | TeSys |
---|---|
Range of product: | TeSys Ultra |
Product name: | TeSys Ultra |
Device short name: | LUCM |
Product or component type: | Multifunction control unit |
Device application: | Motor controlMotor protection |
Product specific application: | Most sophisticated control and protection requirements, with display |
Function available: | Protection against overload and short-circuitManual or automatic resetProtection function alarmProtection against phase failure and phase imbalanceLog functionMonitoring function, indication of main motor parametersOverload, no-load runningEarth fault protectionDifferentiation of thermal overload and magnetic fault |
Product compatibility: | Power base LUB12Power base LUB32Power base LUB38Power base LUB120Power base LUB320Power base LUB380Reversing contactor breaker LU2B12BLReversing contactor breaker LU2B32BLReversing contactor breaker LU2B38BL |
[Ue] rated operational voltage: | 690 V AC |
Network frequency: | 40...60 Hz |
Load type: | 3-phase motor - cooling: self-cooled - setting factory setting3-phase motor - cooling: self-cooled, force cooled - setting settableSingle-phase motor - cooling: self-cooled, force cooled - setting settable |
Utilisation category: | AC-41AC-43AC-44 |
Motor power kW: | 5.5 kW at 400...440 V AC 50/60 Hz for 3 phases motors5.5 kW at 500 V AC 50/60 Hz for 3 phases motors9 kW at 690 V AC 50/60 Hz for 3 phases motors2.2 kW at 400...440 V AC 50/60 Hz for 1 phase motors |
Thermal protection adjustment range: | 3...12 A |
Thermal overload class: | Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to IEC 60947-6-2Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to UL 508 |
Tripping threshold: | 14.2 x Ir +/- 20 % |
[Uc] control circuit voltage: | 24 V DC |
Control circuit voltage limits: | 20...28 V for DC circuit 24 V in operation14.5 V for DC circuit 24 V drop-out |
---|---|
Typical current consumption: | 150 mA at 24 V DC I maximum while closing with LUB12200 mA at 24 V DC I maximum while closing with LUB32200 mA at 24 V DC I maximum while closing with LUB3870 mA at 24 V DC I rms sealed with LUB1275 mA at 24 V DC I rms sealed with LUB3275 mA at 24 V DC I rms sealed with LUB38 |
Heat dissipation: | 1.7 W for control circuit with LUB121.8 W for control circuit with LUB321.8 W for control circuit with LUB380.8 W for external auxiliary circuit |
Operating time: | 35 ms opening with LUB12 for control circuit35 ms opening with LUB32 for control circuit35 ms opening with LUB38 for control circuit75 ms closing with LUB12 for control circuit65 ms closing with LUB32 for control circuit65 ms closing with LUB38 for control circuit |
Physical interface: | RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s |
Return time: | |
Messages display capacity: | 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir |
Reset: | Automatic reset - setting: setting rangeManual - setting: factory settingManual - setting: setting rangeRemote reset - setting: setting range |
Time before reset: | 1...1000 s - reset manual or automatic reset - setting settable120 s - reset manual - setting factory setting |
User language: | English - setting factory settingEnglish, French, German, Italian, Spanish - setting settable |
Information displayed: | Average current (factory setting)Average current (settable)Cause of last 5 faults (settable)Current in phase (settable)Earth leakage current (settable)Phase imbalance (settable)Thermal state of motor (settable) |
Standards: | EN 60947-6-2IEC 60947-6-2UL 60947-4-1, with phase barrierCSA C22.2 No 60947-4-1, with phase barrier |
Product certifications: | CEULCSACCCEACASEFAATEXMarine |
[Ui] rated insulation voltage: | 690 V conforming to IEC 60947-6-2600 V conforming to UL 60947-4-1600 V conforming to CSA C22.2 No 60947-4-1 |
[Uimp] rated impulse withstand voltage: | 6 kV conforming to IEC 60947-6-2 |
Safe separation of circuit: | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 |
Fixing mode: | Plug-in (front face) |
Width: | 45 mm |
Height: | 66 mm |
Depth: | 60 mm |
Net weight: | 0.175 kg |
Compatibility code: | LUCM |
In short
Reference LUCM12BL
Product Name Multifunction control unit, TeSys U, 3-12A, 1P/3P motors, protection & diagnostic, class 5-30, coil 24V DC - LUCM12BL
Range TeSys
Related Categories