SCHNEIDER
circuit breaker Compact NSXm 160A 4P 25kA at 380/415V(IEC) EverLink lug - LV426229
LV426229
Obsolete product, here is the proposed substitution for the reference LV426229 : C12B4TM160L
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSXm |
Range of product: | ComPact NSXm |
Device short name: | NSXm 160B |
Product or component type: | Circuit breaker |
Device application: | ProtectionDistribution |
Poles description: | 4P |
Protected poles description: | 4D |
Neutral position: | Left |
[In] rated current: | 160 A at 40 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-220 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | B 25 kA 415 V AC |
Trip unit name: | TM-D |
Trip unit technology: | Thermal-magnetic |
Trip unit protection functions: | LI |
Control type: | Toggle |
Mounting mode: | By screwsClip-on |
[Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-225 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-220 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 20000 cycles |
Electrical durability: | 10000 cycles at 440 V In20000 cycles at 440 V In/25000 cycles at 690 V In10000 cycles at 690 V In/2 |
Mounting support: | PlateDIN rail |
Connections - terminals: | 1 Everlink lug wire size 2.5...70 mm², flexible copper 1 Everlink lug wire size 2.5...95 mm², rigid or stranded copper |
Connection pitch: | 35 mm with spreaders27 mm without spreaders |
9 mm pitches: | 12 module |
Protection type: | L |
Trip unit rating: | 160 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable |
Long time pick-up adjustment range: | 0.7...1 x In |
Long time delay adjustment type: | Fixed |
Magnetic tripping current: | 1250 A |
Earth-leakage protection: | Without |
Number of slots: | 1 slot(s) for auxiliary switch OF1 slot(s) for alarm switch SD1 slot(s) for voltage release MN or MX |
Width: | 108 mm |
Height: | 137 mm |
Depth: | 80 mm |
Net weight: | 1.42 kg |
Colour: | Grey (RAL 7016) |
In short
Reference LV426229
Product Name circuit breaker Compact NSXm 160A 4P 25kA at 380/415V(IEC) EverLink lug - LV426229
Range Compact
Device function Distribution
Protection
Protection
Related Categories