SCHNEIDER
circuit breaker Compact NSXm Micrologic Vigi 4.1 160A 3P 36kA - EverLink - LV426723
LV426723
Obsolete product, here is the proposed substitution for the reference LV426723 : C12F34V160L
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSXm |
Range of product: | ComPact NSXm |
Device short name: | NSXm 160F |
Product or component type: | Earth leakage circuit breaker |
Device application: | DistributionProtection |
Poles description: | 3P |
Protected poles description: | 3D |
[In] rated current: | 160 A at 40 °C |
[Ue] rated operational voltage: | 440 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | F 36 kA 415 V AC |
Trip unit name: | Micrologic 4.1 |
Trip unit technology: | Electronic |
Trip unit protection functions: | LSoIR |
Control type: | Toggle |
Mounting mode: | By screwsClip-on |
[Ui] rated insulation voltage: | 500 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-236 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-230 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 20000 cycles |
Electrical durability: | 10000 cycles at 440 V In20000 cycles at 440 V In/2 |
Mounting support: | PlateDIN rail |
Connections - terminals: | 1 Everlink lug wire size 2.5...70 mm², fine stranded copper 1 Everlink lug wire size 2.5...95 mm², rigid or stranded aluminium/copper |
Connection pitch: | 35 mm with spreaders27 mm without spreaders |
9 mm pitches: | 9 module |
Protection type: | L |
Trip unit rating: | 160 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
Long time pick-up adjustment range: | 63...160 A |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 5 s at 7.2 x Ir8 s at 6 x Ir200 s at 1.5 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Fixed |
[tsd] short-time delay adjustment range: | 0.02 s |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 2000 A |
Earth-leakage protection: | Integrated |
Residual earth-leakage sensitity adjustment type: | Adjustable |
[I?n] residual earth-leakage sensitive adjustment: | 0.03...5 A |
Earth-leakage sensitivity: | 30 mA for class A100 mA for class A300 mA for class A500 mA for class A1000 mA for class A30 mA for class AC100 mA for class AC300 mA for class AC500 mA for class AC1000 mA for class AC3000 mA for class AC5000 mA for class AC |
Residual earth-leakage time delay adjustment type: | Adjustable |
[?t] residual earth-leakage time delay adjustment: | 0 ms60 ms150 ms500 ms1000 ms |
Neutral protection setting: | No protection1 x Ir0.5 x Ir |
Number of slots: | 1 slot(s) for auxiliary switch OF1 slot(s) for alarm switch SD1 slot(s) for voltage release MN or MX |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
Width: | 108 mm |
Height: | 144 mm |
Depth: | 80 mm |
Net weight: | 1.63 kg |
Colour: | Grey (RAL 7016) |
In short
Reference LV426723
Product Name circuit breaker Compact NSXm Micrologic Vigi 4.1 160A 3P 36kA - EverLink - LV426723
Range Compact
Device function Distribution
Protection
Protection