Range: ComPact
Range of product: ComPact NSX100...250
Product name: Micrologic
Product or component type: Trip unit
Trip unit name: Micrologic 6.2 E
Trip unit technology: Electronic
Range compatibility: ComPact NSX100ComPact NSX160ComPact NSX250
Device application: Distribution
Poles description: 4P
Protected poles description: 3t + OSN4t3t + N/23t
Neutral position: Left
Trip unit protection functions: LSIG
Protection type: L
[In] rated current: 100 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 40...100 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0...0.4 s I²t=off0.1...0.4 s I²t=on
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...12 x In Compact NSX2501.5...15 x In Compact NSX1001.5...15 x In Compact NSX160
Ground-fault pick-up adjustment type: Adjustable
[Ig] ground-fault pick-up adjustment range: 0.2...1 x In for In = 40 A0.4...1 x In for In > 40 AIg enable on/off
Ground-fault time delay adjustment type -tg: Adjustable
[tg] ground-fault time delay adjustment range: 0...0.4 s I²t=off0.1...0.4 s I²t=on
Earth-leakage protection: Without
Neutral protection setting: 0.5 x Ir (3t + N/2)1 x Ir (4t)1.6 x Ir (3t + OSN)No protection (3t)
Zone selective interlocking ZSI: With
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Display type: LCD display
Type of measurement: Energy meter
Communication of data: Power qualityDemand current and powerInstantaneous and demand valuesMaximeters/minimetersProtection and alarm settingsTime-stamped histories and event tablesEnergy meteringMaintenance indicators
Electrical data recording: Maintenance indicators