Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

circuit breaker ComPact NSX100F, 36 kA at 415 VAC, MicroLogic 2.2 trip unit 100 A, 4 poles 4d - LV429780

LV429780

Obsolete product, here is the proposed substitution for the reference LV429780 : C10F42D100
Technical informations
Range: ComPact
Product name: ComPact NSX
Range of product: ComPact NSX100...250
Device short name: NSX100F
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 4P
Protected poles description: 3t3t + N/24t
Neutral position: Left
[In] rated current: 100 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 10 kA at 600 V AC 50/60 Hz conforming to UL 50825 kA at 480 V AC 50/60 Hz conforming to UL 50885 kA at 240 V AC 50/60 Hz conforming to UL 50822 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-28 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: F 36 kA 415 V AC
Trip unit name: Micrologic 2.2
Trip unit technology: Electronic
Trip unit protection functions: LSoI
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-235 kA at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-24 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-212.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 50000 cycles
Electrical durability: 5000 cycles at 690 V In10000 cycles at 690 V In/210000 cycles at 440 V In20000 cycles at 440 V In/2
Mounting support: Backplate
Upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L
Trip unit rating: 100 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 40...100 A
Long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 11 s at 7.2 x Ir16 s at 6 x Ir400 s at 1.5 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 1500 A
Earth-leakage protection: Without
Neutral protection setting: 0.5 x Ir (3t + N/2)1 x Ir (4t)No protection (3t)
Zone selective interlocking ZSI: Without
Number of slots: 5 slot(s)
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Width: 140 mm
Height: 161 mm
Depth: 86 mm
Net weight: 2.4 kg
Compatibility code: NSX100
In short
Reference LV429780
Product Name circuit breaker ComPact NSX100F, 36 kA at 415 VAC, MicroLogic 2.2 trip unit 100 A, 4 poles 4d - LV429780
Range Compact
Device function Distribution
Related Categories