SCHNEIDER
circuit breaker basic frame, ComPact NSX160S, 100 kA at 415 VAC 50/60 Hz, 160 A, without trip unit, 3 poles - LV430391
LV430391
Obsolete product, here is the proposed substitution for the reference LV430391 : C16S3
Technical informations
Range: | ComPact |
---|---|
Range of product: | ComPact NSX100...250 |
Product name: | ComPact NSX |
Device short name: | NSX160S |
Product or component type: | Basic frame |
Device application: | Distribution |
Circuit breaker name: | Compact NSX160S |
Poles description: | 3P |
[In] rated current: | 160 A at 40 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 100 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2120 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-215 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-240 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-290 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | S 100 kA 415 V AC |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-2 |
[Ics] rated service breaking capacity: | 100 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2120 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-215 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-240 kA at 525 V AC 50/60 Hz conforming to IEC 60947-265 kA at 500 V AC 50/60 Hz conforming to IEC 60947-290 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 40000 cycles conforming to IEC 60947-2 |
Electrical durability: | 40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-215000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-220000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-27500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 35 mm |
Protection type: | Without protection |
Width: | 105 mm |
Height: | 161 mm |
Depth: | 86 mm |
Compatibility code: | NSX160 |
In short
Reference LV430391
Product Name circuit breaker basic frame, ComPact NSX160S, 100 kA at 415 VAC 50/60 Hz, 160 A, without trip unit, 3 poles - LV430391
Range Compact
Device function Distribution
Related Categories