Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
100 products at 10% off until 18 November! Find out more
SCHNEIDER

trip unit MicroLogic 2.2 for ComPact NSX 160/250 circuit breakers, electronic, rating 160A, 3 poles 3d - LV430470

LV430470

Obsolete product, here is the proposed substitution for the reference LV430470 : C1632D160
Technical informations
Range: ComPact
Range of product: ComPact NSX100...250
Product name: Micrologic
Product or component type: Trip unit
Trip unit name: Micrologic 2.2
Trip unit technology: Electronic
Range compatibility: ComPact NSX160ComPact NSX250
Device application: Distribution
Poles description: 3P
Protected poles description: 3t
Trip unit protection functions: LSoI
Protection type: L
[In] rated current: 160 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 63...160 A
Long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 11 s at 7.2 x Ir16 s at 6 x Ir400 s at 1.5 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Fixed
[tsd] short-time delay adjustment range: 0.02 s
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 2400 A
Earth-leakage protection: Without
Zone selective interlocking ZSI: Without
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
In short
Reference LV430470
Product Name trip unit MicroLogic 2.2 for ComPact NSX 160/250 circuit breakers, electronic, rating 160A, 3 poles 3d - LV430470
Device function Distribution