Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from December 30th to January 1st! Shipments will resume on January 2nd ⚠️
SCHNEIDER

circuit breaker ComPact NSX160N, 50 kA at 415 VAC, TMD trip unit 125 A, 3 poles 3d - LV430841

LV430841

Obsolete product, here is the proposed substitution for the reference LV430841 : C16N3TM125
Technical informations
Range: ComPact
Product name: ComPact NSX
Range of product: ComPact NSX100...250
Device short name: NSX160N
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3t
[In] rated current: 125 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 10 kA at 600 V AC 50/60 Hz conforming to UL 50885 kA at 240 V AC 50/60 Hz conforming to UL 50810 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-250 kA at 480 V AC 50/60 Hz conforming to UL 50836 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-290 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit protection functions: LI
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-235 kA at 525 V AC 50/60 Hz conforming to IEC 60947-236 kA at 500 V AC 50/60 Hz conforming to IEC 60947-250 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 kA at 440 V AC 50/60 Hz conforming to IEC 60947-290 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 40000 cycles
Electrical durability: 7500 cycles at 690 V In15000 cycles at 690 V In/220000 cycles at 440 V In40000 cycles at 440 V In/2
Mounting support: Backplate
Upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L
Trip unit rating: 125 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable
Long time pick-up adjustment range: 0.7...1 x In
Long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 120...400 s at 1.5 x In15 s at 6 x Ir
Short-time pick-up adjustment type Isd: Fixed
[Isd] short-time pick-up adjustment range: 1250 A
Short-time delay adjustment type: Fixed
Earth-leakage protection: Without
Number of slots: 5 slot(s)
Width: 105 mm
Height: 161 mm
Depth: 86 mm
Net weight: 2.2 kg
Compatibility code: NSX160
In short
Reference LV430841
Product Name circuit breaker ComPact NSX160N, 50 kA at 415 VAC, TMD trip unit 125 A, 3 poles 3d - LV430841
Range Compact
Device function Distribución