Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

trip unit MicroLogic 5.3 A for ComPact NSX 400/630 A circuit breakers, electronic, rating 400A, 4 poles 4d - LV432094

LV432094

Obsolete product, here is the proposed substitution for the reference LV432094 : C4045E400
Technical informations
Range: ComPact
Range of product: ComPact NSX400...630
Product name: Micrologic
Product or component type: Trip unit
Trip unit name: Micrologic 5.3 A
Trip unit technology: Electronic
Range compatibility: ComPact NSX400ComPact NSX630
Device application: Distribution
Poles description: 4P
Protected poles description: 4t3t + OSN3t3t + N/2
Neutral position: Left
Trip unit protection functions: LSI
Protection type: L
[In] rated current: 400 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 160...400 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0...0.4 s I²t=off0.1...0.4 s I²t=on
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...12 x In
Earth-leakage protection: Without
Neutral protection setting: 0.5 x Ir (3t + N/2)1 x Ir (4t)1.6 x Ir (3t + OSN)No protection (3t)
Zone selective interlocking ZSI: With
Local signalling: Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload
Display type: LCD display
Type of measurement: Ammeter
Communication of data: Maintenance indicatorsInstantaneous and demand valuesEnergy meteringTime-stamped histories and event tablesPower qualityDemand current and powerProtection and alarm settingsMaximeters/minimeters
Electrical data recording: Maintenance indicators
In short
Reference LV432094
Product Name trip unit MicroLogic 5.3 A for ComPact NSX 400/630 A circuit breakers, electronic, rating 400A, 4 poles 4d - LV432094
Device function Distribution
Générateur
Related Categories