SCHNEIDER
Circuit breaker ComPact NSX400H, 70kA at 415VAC, MicroLogic 2.3 trip unit 400A, 4 poles 4d - LV432696
LV432696
Obsolete product, here is the proposed substitution for the reference LV432696 : C40H42D400
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSX |
Range of product: | ComPact NSX400...630 |
Device short name: | NSX400H |
Product or component type: | Circuit breaker |
Device application: | Distribution |
Poles description: | 4P |
Protected poles description: | 4t3t3t + N/2 |
Neutral position: | Left |
[In] rated current: | 400 A at 40 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 85 kA at 240 V AC 50/60 Hz conforming to UL 50865 kA at 480 V AC 50/60 Hz conforming to UL 508100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-220 kA at 600 V AC 50/60 Hz conforming to UL 50820 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | H 70 kA 415 V AC |
Trip unit name: | Micrologic 2.3 |
Trip unit technology: | Electronic |
Trip unit protection functions: | LSoI |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-210 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-250 kA at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 15000 cycles |
Electrical durability: | 3000 cycles at 690 V In6000 cycles at 690 V In/26000 cycles at 440 V In12000 cycles at 440 V In/2 |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 45 mm |
Protection type: | L |
Trip unit rating: | 400 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
Long time pick-up adjustment range: | 160...400 A |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 16 s at 6 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Fixed |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 4800 A |
Earth-leakage protection: | Without |
Neutral protection setting: | 0.5 x Ir (3t + N/2)1 x Ir (4t)No protection (3t) |
Zone selective interlocking ZSI: | Without |
Number of slots: | 6 slot(s) |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
Width: | 185 mm |
Height: | 255 mm |
Depth: | 110 mm |
Net weight: | 7.9 kg |
Compatibility code: | NSX400 |
In short
Reference LV432696
Product Name Circuit breaker ComPact NSX400H, 70kA at 415VAC, MicroLogic 2.3 trip unit 400A, 4 poles 4d - LV432696
Range Compact
Device function Distribution
Related Categories