SCHNEIDER
Circuit breaker ComPact NSX400F, 36kA at 415VAC, MicroLogic 4.3-AB Vigi trip unit, 400A, 4 poles 4d - LV433949
LV433949
Obsolete product, here is the proposed substitution for the reference LV433949 : C40F44B400
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSX |
Range of product: | ComPact NSX400...630 |
Device short name: | VigiCompact NSX400F |
Product or component type: | Earth leakage circuit breaker |
Device application: | Special application |
Poles description: | 4P |
Protected poles description: | 3t + N/23t4t |
Neutral position: | Left |
[In] rated current: | 400 A at 40 °C |
[Ue] rated operational voltage: | 440 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | F 36 kA 415 V AC |
Trip unit name: | Micrologic 4.3 AB |
Trip unit technology: | Electronic |
Trip unit protection functions: | LSoIR |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 500 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-236 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-235 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 15000 cycles |
Electrical durability: | 6000 cycles at 440 V In12000 cycles at 440 V In/2 |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 45 mm |
Protection type: | L |
Trip unit rating: | 400 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable 9 settings |
Long time pick-up adjustment range: | 260...400 A |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 11 s at 7.2 x Ir16 s at 6 x Ir400 s at 1.5 x Ir |
Thermal memory: | 20 minutes before and after tripping |
Short-time pick-up adjustment type Isd: | Adjustable |
[Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
Short-time delay adjustment type: | Fixed |
[tsd] short-time delay adjustment range: | 0.02 s |
Instantaneous pick-up adjustment type Ii: | Fixed |
Instantaneous pick-up adjustment range: | 4800 A |
Earth-leakage protection: | Integrated |
Earth-leakage protection class: | Class A |
Residual earth-leakage sensitity adjustment type: | Adjustable |
[I?n] residual earth-leakage sensitive adjustment: | 300 mA500 mA1 A3 A5 A10 A |
Operating mode: | OFF using the I?n rotary switch |
Residual earth-leakage time delay adjustment type: | Adjustable |
[?t] residual earth-leakage time delay adjustment: | 0 ms60 ms150 ms500 ms1 s |
Neutral protection setting: | 0.5 x Ir (3t + N/2)1 x Ir (4t)No protection (3t) |
Zone selective interlocking ZSI: | Without |
Number of slots: | 6 slot(s) |
Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
Width: | 140 mm |
Height: | 161 mm |
Depth: | 86 mm |
Net weight: | 2.4 kg |
Compatibility code: | NSX400 |
In short
Reference LV433949
Product Name Circuit breaker ComPact NSX400F, 36kA at 415VAC, MicroLogic 4.3-AB Vigi trip unit, 400A, 4 poles 4d - LV433949
Range Compact
Device function Application