Circuit breaker ComPact NSX100F AC/DC, 18kA at 415VAC, TMD trip unit 80A, 2 poles 2d - LV438599
LV438599
Obsolete product, here is the proposed substitution for the reference LV438599 : C10F2TM080
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSX |
Range of product: | ComPact NSX100...250ComPact NSX100...250 DC |
Device short name: | NSX100F |
Product or component type: | Circuit breaker |
Device application: | Distribution |
Poles description: | 2P |
Protected poles description: | 2t |
[In] rated current: | 80 A at 40 °C |
[Ue] rated operational voltage: | 690 V AC 50/60 Hz500 V DC |
Network type: | DCAC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 250 V DC 1P conforming to IEC 60947-236 kA Icu at 125 V DC 1P conforming to IEC 60947-236 kA Icu at 500 V DC 2P conforming to IEC 60947-210 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-215 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-218 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | F 18 kA 415 V AC |
Trip unit name: | TM-D |
Trip unit technology: | Thermal-magnetic |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-2 |
[Ics] rated service breaking capacity: | 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-236 kA at 250 V DC conforming to IEC 60947-236 kA at 125 V DC conforming to IEC 60947-236 kA at 500 V DC conforming to IEC 60947-210 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-215 kA at 440 V AC 50/60 Hz conforming to IEC 60947-218 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-236 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 20000 cycles |
Electrical durability: | 10000 cycles at 277 V In20000 cycles at 277 V In/2 |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 35 mm |
Protection type: | for overload protection (thermal) for short-circuit protection (magnetic) |
Trip unit rating: | 80 A at 40 °C |
Long time pick-up adjustment type Ir: | Fixed |
Long time pick-up adjustment range: | 1 In |
Magnetic tripping current: | 640 A |
Earth-leakage protection: | Without |
Width: | 70 mm |
Height: | 161 mm |
Depth: | 86 mm |
Compatibility code: | NSX100 |
In short
Reference LV438599
Product Name Circuit breaker ComPact NSX100F AC/DC, 18kA at 415VAC, TMD trip unit 80A, 2 poles 2d - LV438599
Range Compact
Device function Distribution
Related Categories