Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
ABB

S201M-C16 Miniature Circuit Breaker 1P - C - 16 A - ABB2CDS271001R0164

ABB2CDS271001R0164

€9.13 Excl. Tax
€10.96 Inc. Tax
available In stock more than 25 units – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations

Environment :

  • Ambient air temperature : Operation -25 ... +55 °C : Storage -40 ... +70 °C
  • Reference ambient air temperature : 30 °C
  • Protection class : IP20 IP40 Enclosure with IP40 cover
  • Pollution degree : : 3
  • Environmental conditions : : 28 cycles at 55°C / 90-96% : and 25°C / 95-100
  • Vibration resistance : : 20 cycles with a load of 0.8 In : 5g 5 ... 150 ... 5 Hz
    Shock resistance to IEC 60068-2-27 : : 25g 2 shocks 13 ms

 Dimensions :

  • Width in Number of modular spacers : 1
  • Net product width : 17.5 mm
  • Net product height: 88 mm
  • Net product length: 69 mm
  • Net weight: 0.125 kg
  • Net weight of post: 0.125 kg
  • Installation depth (t2): 69 mm

Certificates and declarations (document number) :

  • Certification agency: EN IEC

Technical:

  • Standards: IEC/EN 60898-1 IEC/EN 60947-2 UL 1077 CSA 22.2 No. 235
  • Trigger Characteristic: C
  • Voltage: according to IEC 60898-1 230/ 400 V AC acc. according to IEC 60898-1 230 V acc. according to IEC 60947-2 230 V AC
  • Operating voltage: Maximum (Incl. Tolerance) 253 V AC Maximum (Incl. Tolerance) 72 V DC Minimum 12 V AC Minimum 12 V DC
  • Rated isolation voltage (Ui): according to IEC/EN 60664-1 440 V
  • Rated shock resistance voltage (Uimp): 4 kV at 2000 m 5 kV at sea level 6.2 kV
  • Dielectric test voltage: 50/60 Hz, 1 min: 2 kV
  • Voltage Type: AC/DC
  • Rated current (In): 16 A
  • Nominal short circuit capacity: (AC) 10 kA (230/ 400 V AC) 10 kA (230 V) 10 kA (400 V) 10 kA
  • Ultimate short-circuit cut-off power (Icu): (133 V AC) 25 kA (230 V AC) 15 kA (230 V) 15 kA (400 V) 15 kA
  • Nominal conditional short circuit current (Inc): (230 V) 15 kA
  • Provide assigned short circuit service break (Ics): (133 V AC) 18.8 kA (230 V AC) 7.5 kA
  • Frequency (f): 50 Hz
  • Assigned frequency (f): 50/ 60 Hz
  • Power loss: 2.5 W at rated operating conditions per pole 2.5 W
  • Power connection: Arbitrary
  • Contact position indication: red ON / green OFF
  • Energy limitation class: 3
  • Electrical endurance: 20000 AC cycle
  • Mechanical endurance: 20000 cycle
  • Number of posts protected: 1
  • Number of poles: 1
  • Overvoltage Category: III
  • Tightening torque: 2.8 N m
  • Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
  • Actuator Marking:I / O
  • Actuator Material: Insulation Group II, Black, Sealable
  • Quality of the material: Insulation Group II, RAL 7035
  • Montage sur rail DIN: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Type of installation: any
  • Recommended Screw Driver: Pozidriv 2
  • Accessories Available: Oui
  • Connecting Capacity: Busbar 10 / 10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm²
  • Installation Size: acc. to DIN 43880 1
  • Terminal Type: Screw Terminals

Technical UL/CSA :

  • UL/CSA maximum operating voltage: 60V DC: 480Y/277V AC
  • Cutting power according to UL1077: (277 V AC) 6 kA (480Y/ 277 V AC) 6 kA: (60 V DC) 10 kA
  • UL/CSA connection capacity: 14-8 AWG busbar 14-4 AWG conductor
  • UL/CSA Torque 18 in-lb
In short
Reference ABB2CDS271001R0164
Product Name S201M-C16 Miniature Circuit Breaker 1P - C - 16 A - ABB2CDS271001R0164
Related Categories