Technical informations
- Technical Specifications
- Rated service breaking capacity (Ics):
- (230 V AC) 50 kA
- (400 V AC) 50 kA
- (440 V AC) 6 kA
- (500 V AC) 6 kA
- (690 V AC) 2 kA
- Ultimate short-circuit breaking capacity (Icu):
- (230 V AC) 75 kA
- (400 V AC) 75 kA
- (440 V AC) 18 kA
- (500 V AC) 15 kA
- (690 V AC) 3 kA
- Instantaneous short-circuit setting current (Ii): 78.8 A
- Setting Range: 4.0 ... 6.3 A
- Rated operational power AC-3 (Pe):
- (400 V) Three-Phase 2.2 kW
- Rated operational power AC-3e (Pe):
- (400 V) Three-Phase 2.2 kW
- Voltage:
- Main Circuit 690 V AC
- Rated operational current (Ie): 6.3 A
- Rated operational current AC-3 (Ie): 6.3 A
- Rated operational current AC-3e (Ie): 6.3 A
- Rated frequency (f):
- Main Circuit 50 Hz
- Main Circuit 60 Hz
- Rated impulse withstand voltage (Uimp):
- Main Circuit 6 kV
- Rated insulation voltage (Ui): 690 V
- Power Loss:
- at Rated Operating Conditions per Pole 0.7 ... 1.8 W
- Number of Poles: 3P
- Conventional free air thermal current (Ith):
- Main Circuit 6.3 A
- Protection Rating:
- Housing IP20
- Main Circuit Terminals IP10
- Pollution Degree: 3
- Electrical Durability: 100,000 cycles
- Mechanical Durability: 100,000 cycles
- Terminal Type: Screw Terminals
- Main Circuit Connection Capacity:
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
- Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
- Flexible 1/2x 0.75 ... 2.5 mm²
- Rigid 1/2x 1 ... 4 mm²
- Tightening Torque:
- Main Circuit 0.8 ... 1.2 N·m
- Wire Stripping Length:
- Main Circuit 9 mm
- Recommended Screwdriver: Pozidriv 2
- Mounting Type:
- 1 ... 6
- DIN Rail Mounting:
- TH35-15 (35 x 15 mm Mounting Rail) according to IEC 60715
- TH35-7.5 (35 x 7.5 mm Mounting Rail) according to IEC 60715
- Minimum Mounting Distance:
- Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
- Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
- Electrical Conductive Board, Vertical 75 mm
- Other Device Same Type, Horizontal 0 mm
- Other Device Same Type, Vertical 150 mm
- Actuator Type: Rotary Handle
- Contact Position Indication: ON / OFF
- Standards:
- IEC/EN 60947-1
- IEC/EN 60947-2
- IEC/EN 60947-4-1
- UL 60947-1
- UL 60947-4-1
- IEC 60335-2-40 A2L
- Rated service breaking capacity (Ics):
- Environment
- Ambient Air Temperature:
- Around the Enclosure 0 ... +40 °C
- Operation -25 ... +70 °C
- Operation Compensated -25 ... +55 °C
- Storage -50 ... +80 °C
- Ambient Air Temperature Compensation: Yes
- Maximum Permissible Operating Altitude: 2000 m
- Shock Resistance According to IEC 60068-2-27:
- 11 ms Pulse 25g
- Resistance to Vibrations:
- 2g 5 ... 150 Hz
- 5g 3 ... 150 Hz
- Ambient Air Temperature: