SCHNEIDER
circuit breaker VigiComPact NSX100F, 36 kA at 415 VAC, TM-D trip unit 63 A, add-on Vigi MH module, 3P 3d - LV429932
LV429932
Obsolete product, here is the list of products that can replace the reference LV429932 :C10F34V100 C11F34V100L
Technical informations
Range: | ComPact |
---|---|
Product name: | ComPact NSX |
Range of product: | ComPact NSX100...250 |
Device short name: | VigiCompact NSX100F |
Product or component type: | Circuit breaker with Vigi add-on |
Device application: | Distribution |
Poles description: | 3P |
Protected poles description: | 3t |
[In] rated current: | 63 A at 40 °C |
[Ue] rated operational voltage: | 440 V AC 50/60 Hz |
Network type: | AC |
Network frequency: | 50/60 Hz |
Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
Utilisation category: | Category A |
Breaking capacity: | 10 kA at 600 V AC 50/60 Hz conforming to UL 50825 kA at 480 V AC 50/60 Hz conforming to UL 50885 kA at 240 V AC 50/60 Hz conforming to UL 50822 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-28 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code: | F 36 kA 415 V AC |
Trip unit name: | TM-D |
Trip unit technology: | Thermal-magnetic |
Trip unit protection functions: | LI |
Control type: | Toggle |
Mounting mode: | Fixed |
[Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage: | 8 kV |
[Ics] rated service breaking capacity: | 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-235 kA at 440 V AC 50/60 Hz conforming to IEC 60947-236 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-24 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-212.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability: | 50000 cycles |
Electrical durability: | 10000 cycles at 690 V In20000 cycles at 690 V In/230000 cycles at 440 V In50000 cycles at 440 V In/2 |
Mounting support: | Backplate |
Upside connection: | Front |
Downside connection: | Front |
Connection pitch: | 35 mm |
Protection type: | L |
Trip unit rating: | 63 A at 40 °C |
Long time pick-up adjustment type Ir: | Adjustable |
Long time pick-up adjustment range: | 0.7...1 x In |
Long time delay adjustment type: | Fixed |
[tr] long-time delay adjustment range: | 120...400 s at 1.5 x In15 s at 6 x Ir |
Short-time pick-up adjustment type Isd: | Fixed |
[Isd] short-time pick-up adjustment range: | 500 A |
Short-time delay adjustment type: | Fixed |
Earth-leakage protection: | With |
Earth-leakage add-on module name: | MH |
Earth-leakage protection class: | Class A |
Residual earth-leakage sensitity adjustment type: | Adjustable 5 settings |
[I?n] residual earth-leakage sensitive adjustment: | 0.03...10 A |
Residual earth-leakage time delay adjustment type: | Adjustable 4 settings |
Number of slots: | 6 slot(s) |
Width: | 105 mm |
Height: | 236 mm |
Depth: | 86 mm |
Product weight: | 2.05 kg |
Compatibility code: | NSX100 |
In short
Reference LV429932
Product Name circuit breaker VigiComPact NSX100F, 36 kA at 415 VAC, TM-D trip unit 63 A, add-on Vigi MH module, 3P 3d - LV429932
Range Compact
Device function Distribution