Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
SCHNEIDER

Star-Delta Timing Relay - 0.05s…300s - 24V DC / 24…240V AC - 1C/O - RE22R1QCMU

RE22R1QCMU

€41.36 Excl. Tax
€49.63 Inc. Tax
available In stock – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 200€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa fintecture alma applepay
Technical informations
Range of product: Harmony Timer Relays
Product or component type: Single function relay
Discrete output type: Relay
Device short name: RE22
Nominal output current: 8 A
[Uc] control circuit voltage: 24 V24...240 V
Contacts type and composition: 1 C/O
Connections - terminals: Screw connectors
[In] rated current: 5 A
Output type: Relay
Contacts type and composition: 1 C/O timed contact, cadmium free
Time delay type: Star-delta
Time delay range: 10...100 s3...30 s0.1...1 s0.3...3 s0.05...0.5 s1...10 s30...300 s
Control type: Rotary knobDiagnostic button
[Us] rated supply voltage: 24 V DC24...240 V AC 50/60 Hz
Input voltage:
Voltage range: 0.85...1.1 Us
Supply frequency: 50...60 Hz +/- 5 %
Connections - terminals: Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable endScrew terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque: 0.6...1 N.m conforming to IEC 60947-1
Housing material: Self-extinguishing
Repeat accuracy: +/- 0.5 % conforming to IEC 61812-1
Temperature drift: +/- 0.05 %/°C
Voltage drift: +/- 0.2 %/V
Setting accuracy of time delay: +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Insulation resistance: 100 MOhm at 500 V DC conforming to IEC 60664-1
Reset time: 120 ms on de-energisation
Immunity to microbreaks: 10 ms
Power consumption in VA: 35 VA at 240 V AC
Power consumption in W: 0.6 W at 24 V DC
Switching capacity in VA: 2000 VA
Minimum switching current: 10 mA at 5 V DC
Maximum switching current: 8 A
Maximum switching voltage: 250 V AC
Electrical durability: 100000 cycles, 8 A at 250 V, AC-1100000 cycles, 2 A at 24 V, DC-1
Mechanical durability: 10000000 cycles
[Uimp] rated impulse withstand voltage: 5 kV for 1.2...50 µs conforming to IEC 60664-1
Maximum delay response: 100 ms
Creepage distance: 4 kV/3 conforming to IEC 60664-1
Overvoltage category: III conforming to IEC 60664-1
Safety reliability data: MTTFd = 285.3 yearsB10d = 270000
Mounting position: Any position
Mounting support: 35 mm DIN rail conforming to EN/IEC 60715
Status LED: LED backlight green (steady) for dial pointer indicationLED yellow (steady) for output relay energisedLED yellow (fast flashing) for timing in progress and output relay de-energisedLED yellow (slow flashing) for timing in progress and output relay energised
Width: 22.5 mm
Product weight: 0.08 kg
Time delay type: Qc
Contacts type and composition: 1 C/O
Functionality: Star-delta starter timing
In short
Reference RE22R1QCMU
Product Name Star-Delta Timing Relay - 0.05s…300s - 24V DC / 24…240V AC - 1C/O - RE22R1QCMU
Related Categories