Informations techniques
Device application : | Distribution |
---|---|
Range : | Acti 9 |
Range of product : | IC60 |
Product name : | Acti 9 iC60 |
Product or component type : | Miniature circuit-breaker |
Device short name : | IC60L |
Poles description : | 2P |
Number of protected poles : | 2 |
[In] rated current : | 50 A |
Network type : | DCAC |
Trip unit technology : | Thermal-magnetic |
Curve code : | B |
Breaking capacity code : | L |
Breaking capacity : | 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-215 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-230 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-270 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-270 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-220 kA Icu at |
Utilisation category : | Category A conforming to EN 60947-2Category A conforming to IEC 60947-2 |
Suitability for isolation : | Yes conforming to EN 60947-2Yes conforming to IEC 60947-2 |
Standards : | IEC 60947-2EN 60947-2 |
Network frequency : | 50/60 Hz |
---|---|
[Ue] rated operational voltage : | 220...240 V AC 50/60 Hz380...415 V AC 50/60 Hz440 V AC 50/60 Hz12...133 V AC 50/60 Hz72...125 V DC |
Magnetic tripping limit : | 4 x In +/- 20 % |
[Ics] rated service breaking capacity : | 15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz35 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz35 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz20 kA 100 % conforming to EN 60947-2 - 72...125 V DC20 kA 100 % conforming to IEC 60947-2 - 72...125 V DC |
[Ui] rated insulation voltage : | 500 V AC 50/60 Hz conforming to EN 60947-2500 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage : | 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2 |
Contact position indicator : | Yes |
Control type : | Toggle |
Local signalling : | Trip indicator |
Mounting mode : | Fixed |
Mounting support : | DIN rail |
Comb busbar and distribution block compatibility : | Top or bottom: YES |
9 mm pitches : | 4 |
Height : | 85 mm |
Width : | 36 mm |
Depth : | 78.5 mm |
Product weight : | 0.25 kg |
Colour : | White |
Mechanical durability : | 20000 cycles |
Electrical durability : | 10000 cycles |
Connections - terminals : | Single terminal (top or bottom) 1...35 mm² rigidSingle terminal (top or bottom) 1...25 mm² flexible |
Wire stripping length : | 14 mm for top or bottom connection |
Tightening torque : | 3.5 N.m top or bottom |
Earth-leakage protection : | Separate block |
Compatibility code : | IC60 |
Market segment : | ResidentialSmall commercial |